EFFEBI-PRESS

ANNEX 4.

SYSTEM:

CUSTOMER:

PERFORMER:

TEST REPORT WITH WATER FOR WET SPRINKLER FIRE FIGHTING SYSTEM

_____________________________________________________________________________________

_____________________________________________________________________________________

_____________________________________________________________________________________

Following the test it is hereby declared that:

The entire system was visually checked to make sure that all the connections have been made in accordance with the

best working standards.

The pipework has been completely aired out.

• Water temperature =

• Room temperature =

• Temperature difference ∆T =

_____ °C

_____ °C

_____ °C (must be ≤ 10 °C)

Seal test

Max. operating pressure =

_____ bar

Test pressure =

_____ bar

(the higher between 15 bar and max. operating pressure x 1,5)

Duration of the test =

_____ minutes

(must be ≥ 120 minutes)

The ducts are watertight (∆p = 0)

Place

_______________________________

Date

_______________________________

Signature of the customer or representative:

_______________________________

Signature of the performer or representative:

_______________________________

Manuale Tecnico [profilo V]

59

Technical Guide [V-Profile]