the thermostatic mixer or the recycling circuit
do not works correctly during the normal use
of mixed water
see the remedies for the mod. ECOSAN
and ECOSYSTEM
the recycling circuit temperature do not reach
the established temperature for the disin-
fection
hot water temperature insufficient inside the
accumulation-tank
check water temperature in the boiler
magnetic valves are locked
clean or replace the magnetic valve that do
not works
circulation pump do not works
clean or replace the circulation pump
digital switch do not programmed correctly
re-program the digital switch or replace it if
do not works
digital switch do not works
after the thermic disinfection the temperature
of the recycling ring do not reach the establi-
shed temperature for the normal use of the
mixed water
magnetic valves are locked
clean or replace the magnetic valve that do
not works
digital switch do not programmed correctly
re-program the digital switch or replace it if
do not works
digital switch do not works
sudden changes in temperature
foreign body inside the cartridge
remove the handle, unscrew the cover, get out
upward to extract the cartridge and rinse it
thoroughly with water
check the O-ring of the valve and replace if
necessary
water with too much calcareous
leave the thermostatic cartridge to soak in
vinegar
there are differences in pressure or flow rate
between the hot and cold water system
the cause of this imbalance must be found in
the system. For example: a non-return valve
may be jammed or secondary offtakes may
be reducing the flow rate in the pipes to the
mixer
the temperature of the mixed water remain
high (do not go down) although the adjusting
knob is screwed till the end of stroke (towards
the cold)
foreign body inside the cartridge
clean or replace the magnetic valve that do
not works
majority of cold water in the system
close partially the cold gate valve
the mixer supply only cold water
majority of hot water in the system
close partially the hot gate valve
515