ECOSAN ANTILEGIONELLA

ECOMEDICAL

FAULT

CAUSE

REMEDY

the thermostatic mixer or the recycling circuit

do not works correctly during the normal use

of mixed water

see the remedies for the mod. ECOSAN

and ECOSYSTEM

the recycling circuit temperature do not reach

the established temperature for the disin-

fection

hot water temperature insufficient inside the

accumulation-tank

check water temperature in the boiler

magnetic valves are locked

clean or replace the magnetic valve that do

not works

circulation pump do not works

clean or replace the circulation pump

digital switch do not programmed correctly

re-program the digital switch or replace it if

do not works

digital switch do not works

after the thermic disinfection the temperature

of the recycling ring do not reach the establi-

shed temperature for the normal use of the

mixed water

magnetic valves are locked

clean or replace the magnetic valve that do

not works

digital switch do not programmed correctly

re-program the digital switch or replace it if

do not works

digital switch do not works

MINIECO – UNIVERSAL – MULTI

sudden changes in temperature

foreign body inside the cartridge

remove the handle, unscrew the cover, get out

upward to extract the cartridge and rinse it

thoroughly with water

check the O-ring of the valve and replace if

necessary

water with too much calcareous

leave the thermostatic cartridge to soak in

vinegar

there are differences in pressure or flow rate

between the hot and cold water system

the cause of this imbalance must be found in

the system. For example: a non-return valve

may be jammed or secondary offtakes may

be reducing the flow rate in the pipes to the

mixer

the temperature of the mixed water remain

high (do not go down) although the adjusting

knob is screwed till the end of stroke (towards

the cold)

foreign body inside the cartridge

clean or replace the magnetic valve that do

not works

majority of cold water in the system

close partially the cold gate valve

the mixer supply only cold water

majority of hot water in the system

close partially the hot gate valve

515