MITSUBISHI ELECTRIC / REPLACE TECHNOLOGY - COMMERCIALE
54
Distributore del
refrigerante
<SISTEMI TWIN>
Total lenght A+B+C
M125,M140 ≤ 65m
A
UNITÀ
INTERNA
Distributore del
refrigerante
<SISTEMI TRIPLE>
Total lenght A+B+C+D
M140 ≤ 65m
A
UNITÀ
INTERNA
B
B
C
C
D
Lunghezza massima delle tubazioni (M100, M125, M140)
M100(50x2)
M125(60x2) + M140(71x2)
Linea
Principale
(mm) [A]
Linea liquido
ø9.52
ø9.52
ø12.7
ø9.52
ø9.52
ø12.7
Linea gas
ø15.88
ø19.05
ø19.05
ø15.88
ø19.05
ø19.05
Linee
secondarie
(mm) [B, C]
Linea
liquido
ø6.35
Standard size
55m
[30m]
50m
[30m]
30m
[10m]
Linea gas
ø12.7
Linea
liquido
ø9.52
50m
[30m]
50m
[30m]
50m
[30m]
Standard size
65m
[30m]
50m
[30m]
30m
[15m]
Linea gas
ø15.88
Lunghezza massima delle tubazioni
M140(50x3)
Linea
Principale
(mm) [A]
Linea liquido
ø9.52
ø9.52
ø12.7
Linea gas
ø15.88
ø19.05
ø19.05
Linee
secondarie
(mm) [B, C, D]
Linea
liquido
ø6.35
Standard size
65m
[30m]
50m
[30m]
30m
[15m]
Linea gas
ø12.7
Linea
liquido
ø9.52
50m
[30m]
50m
[30m]
30m
[15m]
Linea gas
ø15.88
UNITÀ
INTERNA
UNITÀ
INTERNA
UNITÀ
INTERNA
UNITÀ
INTERNA
UNITÀ
INTERNA
H
h
H
h