PILLAR HYRDANTS
PILLAR HYDRANTS
Pillar hydrant is a device connected to a pressurized water supply
designated to supply water for
firefighting during all phases of the fire.
It has a barrel which emerges from below the ground level, allowing
above ground connection of equipment for firefighting purposes.
Following customer’s speci
fication hydrant can be supplied:
– without connections: outlets are female BSP threaded. In this case the
purchaser can provide by himself the required connection;
– with connection and plug: available connections Bocciolone can
normally supply are UNI (Italian standard), DSP (French standard),
BS 336 (British standard), NH (American standard), STORZ (German
standard), GOST (Russian standard), UNE (Spanish standard).
Following customer’s requirements each hydrant can be supplied with:
– two side outlets;
– two side outlets and one front outlet for fire truck connec
tion.
Each hydrant is supplied with antifreeze drainage system. The drainage
system automatically drains the water inside the hydrant when it is closed
and prevents internal surface of the shell from corrosion. All parts of the
drainage system are made of corrosion resistant materials.
All components are in cast iron and they are duly coated to protect them
against corrosion.
Our production program includes three styles of hydrants:
Style “EUR”
Made from cast iron. It comes in two models:
– type A: without break system: recommended in the area where
hydrant cannot be hit by car or truck (such as green areas). It is
cheaper and it performs better during pressure drop test;
– type C: with break system: recommended when possibility of
collisions is believed to be more real (on the road for instance).
The break system is a mechanism which allows the above ground
part to separate from the below part when subject to impact whilst
maintaining the seal of the main valve. The hydrant is designed to
allow replacing the above part without excavation work.
Style “MONOTUBO”
Barrel is manufactured in galvanized steel, available only without break
system.
Style “66FM”
American standard: barrel in cast iron, according to AWWA C 502, UL
listed, FM approved, available only with break system.
Vandal-proof device for pillar hydrant
PATENT PENDING
14 Bocciolone Antincendio · Fire Fighting Equipment